Zero power factor curve

Article snapshot taken from Wikipedia with creative commons attribution-sharealike license. Give it a read and then ask your questions in the chat. We can research this topic together.

This is the current revision of this page, as edited by Citation bot (talk | contribs) at 06:11, 28 December 2024 (Added date. | Use this bot. Report bugs. | Suggested by BorgQueen | Linked from User:AlexNewArtBot/PhysicsSearchResult | #UCB_webform_linked 246/351). The present address (URL) is a permanent link to this version.

Revision as of 06:11, 28 December 2024 by Citation bot (talk | contribs) (Added date. | Use this bot. Report bugs. | Suggested by BorgQueen | Linked from User:AlexNewArtBot/PhysicsSearchResult | #UCB_webform_linked 246/351)(diff) ← Previous revision | Latest revision (diff) | Newer revision → (diff)
A diagram with multiple synchronous machine curves; Zero power factor curve is the middle
This article needs additional citations for verification. Please help improve this article by adding citations to reliable sources. Unsourced material may be challenged and removed.
Find sources: "Zero power factor curve" – news · newspapers · books · scholar · JSTOR (December 2024) (Learn how and when to remove this message)

The zero power factor curve (also zero power factor characteristic, ZPF, ZPFC) of a synchronous generator is a plot of the output voltage as a function of the excitation current or field using a zero power factor (purely inductive) load that corresponds to rated voltage at rated current (1 p.u.). The curve is typically plotted alongside the open-circuit characteristic.

Obtained by measuring the terminal voltage when the current has a zero power factor current using a pure inductive load that could be regulated to compensate the reactive power of the generator EMF.

The curve is obtained by rotating the generator at the rated RPM with the output terminals connected to the unity load, varying the excitation field and recording the output voltage.

Potier Triangle

The ZPFC could be used together with the open-circuit saturation curve in Potier Triangle method.

The zero power characteristic is similar to the open-circuit characteristic but shifted down by α {\displaystyle \alpha } .