Misplaced Pages

Limiting oxygen concentration

Article snapshot taken from Wikipedia with creative commons attribution-sharealike license. Give it a read and then ask your questions in the chat. We can research this topic together.
Flammability diagram, green dotted line shows safe purging of an air-filled vessel, first with nitrogen, then with methane, to avoid the flammable region. The limiting oxygen concentration is shown in the lower right of the diagram.

The limiting oxygen concentration (LOC), also known as the minimum oxygen concentration (MOC), is defined as the limiting concentration of oxygen below which combustion is not possible, independent of the concentration of fuel. It is expressed in units of volume percent of oxygen. The LOC varies with pressure and temperature. It is also dependent on the type of inert (non-flammable) gas.

Limiting oxygen concentration for selected gases and two inerts (volume percent oxygen)
Gas or vapor Nitrogen / Air Carbon dioxide / Air
Hydrogen 5 5.2
Methane 12 14.5
Ethane 11 13.5
Propane 11.5 14.5
n-Butane 12 14.5
Isobutane 12 15

Limiting oxygen concentration for solid materials

Material Nitrogen/Air
PE-HD 16.0
PP 16.0
PMMA 15.9
PVC 16.9
PE-LD 15.9
Fir wood 17.0
Corrugated board 15.0
Cardboard palletised 15.0
Paper 14.1

The effect of increasing the concentration of inert gas can be understood by viewing the inert as thermal ballast that quenches the flame temperature to a level below which the flame cannot exist. Carbon dioxide is therefore more effective than nitrogen due to its higher molar heat capacity.

The concept has important practical use in fire safety engineering. For instance, to safely fill a new container or a pressure vessel with flammable gases, the atmosphere of normal air (containing 20.9 volume percent of oxygen) in the vessel would first be flushed (purged) with nitrogen or another non-flammable inert gas, thereby reducing the oxygen concentration inside the container. When the oxygen concentration is below the LOC, flammable gas can then be safely admitted to the vessel, because the possibility of internal explosion has been eliminated.

The limiting oxygen concentration is a necessary parameter when designing hypoxic air fire prevention systems.

See also

Sources

Monographs

  • Green, Don W.; Robert H. Perry (October 23, 2007). Perry's Chemical Engineers' Handbook. McGraw-Hill Professional; 8 edition. ISBN 978-0-07-142294-9. Chapter 23
  • Drysdale, Dougal (1985). An Introduction to Fire Dynamics. Wiley. ISBN 0-471-90613-1.

References

  1. Perry
  2. Drysdale
  3. Perry 8.ed:23-9
  4. VdS 3527en:2007 - Inerting and Oxygen Reduction Systems, Planning and Installation. VdS. 2007.
  5. Drysdale:84-85
  6. Drysdale:92
Categories: