Revision as of 04:29, 2 August 2005 editLight current (talk | contribs)30,368 edits split long sentence into 2/ remove conjecture from apps/ tidied desc of buzzer operation← Previous edit | Latest revision as of 04:36, 27 June 2024 edit undo98.115.164.53 (talk) →Protective relays: stylr | ||
Line 1: | Line 1: | ||
{{short description|Electrically-operated switch}} | |||
] | |||
{{About|the electrical component}} | |||
A '''relay''' is an electrical ] that opens and closes automatically under control of another electrical circuit. It can therefore be considered, in a broad sense, to be a form of electrical ]. In the original form, the switch is operated by an ] to open or close one or many sets of contacts. It was invented by ] in ]. | |||
] | |||
] | |||
] | |||
] | |||
A '''relay''' is an ]ally operated ]. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple ], such as make contacts, break contacts, or combinations thereof. | |||
These contacts can be either '''normally-open''', '''normally-closed''', or '''change-over''' contacts. | |||
*Normally-open contacts disconnect the circuit until the relay is activated. | |||
*Normally-closed contacts connect the circuit until the relay is activated. | |||
*Change-over contacts control two circuits: one that is normally connected and one that is normally disconnected. Activating the relay flips the connections, disconnecting the normally-connected circuit and connecting the normally-disconnected circuit. | |||
Relays are used where it is necessary to control a circuit by an independent low-power signal, or where several circuits must be controlled by one signal. Relays were first used in long-distance ] circuits as signal repeaters: they refresh the signal coming in from one circuit by transmitting it on another circuit. Relays were used extensively in ]s and early computers to perform logical operations. | |||
== Operation == | |||
The traditional ] form of a relay uses an ] to close or open the contacts, but relays using other operating principles have also been invented, such as in ]s which use ] properties for control without relying on ]. Relays with calibrated operating characteristics and sometimes multiple operating coils are used to protect electrical circuits from overload or faults; in modern electric power systems these functions are performed by digital instruments still called '']s'' or '']s''. | |||
When a ] flows through the ], the resulting ] attracts an armature that is mechanically linked to a moving contact. The movement either makes or breaks a connection with a fixed contact. When the current is switched off, the armature is usually returned by a ] to its resting position. ]ing relays exist that require operation of a second coil to reset the contact position. | |||
Latching relays require only a single pulse of control power to operate the switch persistently. Another pulse applied to a second set of control terminals, or a pulse with opposite polarity, resets the switch, while repeated pulses of the same kind have no effects. Magnetic latching relays are useful in applications when interrupted power should not affect the circuits that the relay is controlling. | |||
By analogy with the functions of the original electromagnetic device, a solid-state relay operates a ] or other solid-state switching device with a ] or ] to trigger it. | |||
== History == | |||
Relays may also be operated by heat where a coil heats a bi-metal strip to open contacts, or where a solder pot melts, releasing a spring to operate contacts. Such heat-activated relays are commonly used for motor circuit protection. | |||
Electrical relays got their start in application to ]s. American scientist ] is often cited to have invented a relay in 1835 in order to improve his version of the ], developed earlier in 1831.<ref>{{cite book|title=Icons of Invention: The Makers of the Modern World from Gutenberg to Gates|publisher=ABC-CLIO|url=https://books.google.com/books?id=WKuG-VIwID8C&q=Invention+of+the+relay&pg=PA153|page=153|isbn=9780313347436|year=2009}}</ref><ref>{{cite web|title=The electromechanical relay of Joseph Henry|publisher=Georgi Dalakov|url=http://history-computer.com/ModernComputer/Basis/relay.html|access-date=2012-06-21|archive-url=https://web.archive.org/web/20120618121911/http://history-computer.com/ModernComputer/Basis/relay.html|archive-date=2012-06-18|url-status=dead}}</ref><ref>{{cite book|title=Scientific American Inventions and Discoveries: All the Milestones in Ingenuity--From the Discovery of Fire to the Invention of the Microwave Oven|publisher=John Wiley & Sons|url=https://books.google.com/books?id=pDbQVE3IdTcC&q=relay+Joseph+Henry+1835&pg=PA311|page=311|isbn=9780471660248|date=2005-01-28}}</ref><ref>{{cite book| title=Joseph Henry: His Life and Work| url=https://archive.org/details/josephhenryhisli0000coul| url-access=registration| author=Thomas Coulson | publisher =Princeton University Press| location = Princeton| year = 1950}}</ref> | |||
However, an official patent was not issued until 1840 to ] for his telegraph, which is now called a relay. The mechanism described acted as a digital amplifier, repeating the telegraph signal, and thus allowing signals to be propagated as far as desired.<ref name="Patent1647">{{cite patent|country=US|number=1647|title=Improvement in the Mode of Communicating Information by Signals by the Application of Electromagnetism|pubdate=June 20, 1840|inventor1-last=Morse|inventor1-first=Samuel E.B.|url=http://www.google.com/patents?id=Xx5AAAAAEBAJ&printsec=abstract&zoom=4&dq=1647}} {{Cite web |url=http://www.google.com/patents?id=Xx5AAAAAEBAJ&printsec=abstract&zoom=4&dq=1647 |title=Patent US1647 - IMPROVEMENT IN THE MODE OF COMMUNICATING INFORMATION BY SIGNALS BY THE - Google Patents |access-date=September 6, 2011 |archive-date=May 24, 2012 |archive-url=https://web.archive.org/web/20120524081816/http://www.google.com/patents?id=Xx5AAAAAEBAJ&printsec=abstract&zoom=4&dq=1647 |url-status=bot: unknown }}</ref> | |||
The word ''relay'' appears in the context of electromagnetic operations from 1860 onwards.<ref>{{cite web|title=Relay|url=http://www.etymonline.com/index.php?allowed_in_frame=0&search=relay&searchmode=none|website=EtymOnline.com}}</ref> | |||
== Basic design and operation == | |||
] | |||
], arcing causes degradation of the switch contacts]] | |||
] | |||
A simple electromagnetic relay consists of a coil of wire wrapped around a ] (a solenoid), an iron yoke which provides a low ] path for magnetic flux, a movable iron ], and one or more sets of contacts (there are two contacts in the relay pictured). The armature is hinged to the yoke and mechanically linked to one or more sets of moving contacts. The armature is held in place by a ] so that when the relay is de-energized there is an air gap in the magnetic circuit. In this condition, one of the two sets of contacts in the relay pictured is closed, and the other set is open. Other relays may have more or fewer sets of contacts depending on their function. The relay in the picture also has a wire connecting the armature to the yoke. This ensures continuity of the circuit between the moving contacts on the armature, and the circuit track on the ] (PCB) via the ], which is soldered to the PCB. | |||
When an ] is passed through the coil it generates a ] that activates the armature, and the consequent movement of the movable contact(s) either makes or breaks (depending upon construction) a connection with a fixed contact. If the set of contacts was closed when the relay was de-energized, then the movement opens the contacts and breaks the connection, and vice versa if the contacts were open. When the current to the coil is switched off, the armature is returned by a force, approximately half as strong as the magnetic force, to its relaxed position. Usually this force is provided by a spring, but gravity is also used commonly in industrial motor starters. Most relays are manufactured to operate quickly. In a low-voltage application this reduces noise; in a high voltage or current application it reduces ]. | |||
] | |||
When the coil is energized with ], a ] or ] ] is often placed across the coil to dissipate the energy from the collapsing magnetic field (]) at deactivation, which would otherwise generate a ] dangerous to ] circuit components. Such diodes were not widely used before the application of ]s as relay drivers, but soon became ubiquitous as early ] were easily destroyed by this surge. Some automotive relays include a diode inside the relay case. Resistors, while more durable than diodes, are less efficient at eliminating voltage spikes generated by relays<ref>{{cite web |title=Understanding Relays & Wiring Diagrams |url=https://www.swe-check.com.au/editorials/understanding_relays.php |website=Swe-Check |access-date=16 December 2020}}</ref> and therefore not as commonly used. | |||
] | |||
If the relay is driving a large, or especially a ] load, there may be a similar problem of surge currents around the relay output contacts. In this case a snubber circuit (a capacitor and resistor in series) across the contacts may absorb the surge. Suitably rated capacitors and the associated resistor are sold as a single packaged component for this commonplace use. | |||
If the coil is designed to be energized with ] (AC), some method is used to split the flux into two out-of-phase components which add together, increasing the minimum pull on the armature during the AC cycle. Typically this is done with a small copper "shading ring" crimped around a portion of the core that creates the delayed, out-of-phase component,<ref>{{cite web |title = Art & Science of Protective Relaying, Chapter 2, GE Consumer & Electrical |last= Mason |first= C. R. |url = http://www.gedigitalenergy.com/multilin/notes/artsci/ |access-date = October 9, 2011}}</ref> which holds the contacts during the zero crossings of the control voltage.<ref>{{cite conference |conference=Electrical Contacts |title=Design of Shading Coils for Minimizing the Contact Bouncing of AC Contactors |url=https://www.researchgate.net/publication/224355001 |first1=J.R. |last1=Riba |first2=A.G. |last2=Espinosa |first3=J. |last3=Cusidó |first4=J.A. |last4=Ortega |first5=L. |last5=Romeral |date=November 2008 |access-date=2018-01-07 |page=130}}</ref> | |||
Contact materials for relays vary by application. Materials with low contact resistance may be oxidized by the air, or may tend to "stick" instead of cleanly parting when opening. Contact material may be optimized for low electrical resistance, high strength to withstand repeated operations, or high capacity to withstand the heat of an arc. Where very low resistance is required, or low thermally-induced voltages are desired, gold-plated contacts may be used, along with palladium and other non-oxidizing, semi-precious metals. Silver or silver-plated contacts are used for signal switching. Mercury-wetted relays make and break circuits using a thin, self-renewing film of liquid mercury. For higher-power relays switching many amperes, such as motor circuit contactors, contacts are made with a mixtures of silver and cadmium oxide, providing low contact resistance and high resistance to the heat of arcing. Contacts used in circuits carrying scores or hundreds of amperes may include additional structures for heat dissipation and management of the arc produced when interrupting the circuit.<ref>Ian Sinclair, ''Passive Components for Circuit Design'', Elsevier, 2000 {{ISBN|008051359X}}, pp. 161–164</ref> Some relays have field-replaceable contacts, such as certain machine tool relays; these may be replaced when worn out, or changed between normally open and normally closed state, to allow for changes in the controlled circuit.<ref>{{cite book |first=Joseph E. |last=Fleckenstein |title=Three-Phase Electrical Power |publisher=CRC Press |date=2017 |isbn=978-1498737784 |page=321}}</ref> | |||
== Terminology == | |||
] | |||
Since relays are ]es, the terminology applied to switches is also applied to relays; a relay switches one or more ''poles'', each of whose ] can be ''thrown'' by energizing the coil. Normally open (NO) contacts connect the circuit when the relay is activated; the circuit is disconnected when the relay is inactive. Normally closed (NC) contacts disconnect the circuit when the relay is activated; the circuit is connected when the relay is inactive. All of the contact forms involve combinations of NO and NC connections. | |||
The National Association of Relay Manufacturers and its successor, the Relay and Switch Industry Association define 23 distinct ] found in relays and switches.<ref>Section 1.6, Engineers' Relay Handbook, 5th ed, Relay and Switch Industry Association, Arlington, VA; 3rd ed, National Association of Relay Manufacturers, Elkhart Ind., 1980; 2nd Ed. Hayden, New York, 1966; large parts of the 5th edition are on line {{Webarchive|url=https://web.archive.org/web/20170705143411/http://www.esterline.com/powersystems/DesignReference/RelayHandbook.aspx |date=2017-07-05 }}.</ref> Of these, the following are commonly encountered: | |||
* ''SPST-NO'' (Single-Pole Single-Throw, Normally-Open) relays have a single '']'' or ''make'' contact. These have two terminals which can be connected or disconnected. Including two for the coil, such a relay has four terminals in total. | |||
* ''SPST-NC'' (Single-Pole Single-Throw, Normally-Closed) relays have a single '']'' or ''break'' contact. As with an SPST-NO relay, such a relay has four terminals in total. | |||
* ''SPDT'' (Single-Pole Double-Throw) relays have a single set of '']'', ''break before make'' or ''transfer'' contacts. That is, a common terminal connects to either of two others, never connecting to both at the same time. Including two for the coil, such a relay has a total of five terminals. | |||
* ''DPST'' – Double-Pole Single-Throw relays are equivalent to a pair of SPST switches or relays actuated by a single coil. Including two for the coil, such a relay has a total of six terminals. The poles may be '']'' or '']'' (or one of each; the designations ''NO'' and ''NC'' should be used to resolve the ambiguity). | |||
* ''DPDT'' – Double-Pole Double-Throw relays have two sets of '']'' contacts. These are equivalent to two SPDT switches or relays actuated by a single coil. Such a relay has eight terminals, including the coil | |||
* ] – make before break<ref name=":0">{{Cite journal|last=Alexandrovich|first=George|title=The Audio Engineer's Handbook|url=https://www.americanradiohistory.com/Archive-DB-Magazine/60s/DB-1968-09.pdf|journal=Db: The Sound Engineering Magazine|volume=September 1968|pages=10}}</ref> | |||
* ] – combination of D and B<ref name=":0" /> | |||
The ''S'' (''single'') or ''D'' (''double'') designator for the pole count may be replaced with a number, indicating multiple contacts connected to a single ]. For example, 4PDT indicates a four-pole double-throw relay that has 12 switching terminals. | |||
''EN 50005'' are among applicable standards for relay terminal numbering; a typical EN 50005-compliant SPDT relay's terminals would be numbered 11, 12, 14, A1 and A2 for the C, NC, NO, and coil connections, respectively.<ref>EN 50005:1976 | |||
"Specification for low voltage switchgear and controlgear for industrial use. Terminal marking and distinctive number. General rules." (1976). In the UK published by BSI as BS 5472:1977.</ref> | |||
] defines contact numbers in relays for automotive use: | |||
* 85 = relay coil - | |||
* 86 = relay coil + | |||
* 87 = to load (normally open) | |||
* 87a = to load (normally closed) | |||
* 30 = battery + | |||
== Types == | |||
{{split|List of relay types|date=September 2021}} | |||
=== Coaxial relay === | |||
Where radio transmitters and receivers share one antenna, often a coaxial relay is used as a TR (transmit-receive) relay, which switches the antenna from the receiver to the transmitter. This protects the receiver from the high power of the transmitter. Such relays are often used in ]s which combine transmitter and receiver in one unit. The relay contacts are designed not to reflect any radio frequency power back toward the source, and to provide very high isolation between receiver and transmitter terminals. The ] of the relay is matched to the ] impedance of the system, for example, 50 ohms.<ref>Ian Sinclair, ''Passive Components for Circuit Design'', Newnes, 2000 {{ISBN|008051359X}}, page 170</ref> | |||
=== Contactor === | |||
A ] is a heavy-duty relay with higher current ratings,<ref>{{cite book |editor1-first=Terrell |editor1-last=Croft |editor2-first=Wilford |editor2-last=Summers |title=American Electricians' Handbook |edition=Eleventh |publisher=McGraw Hill |location=New York |date=1987 |isbn=978-0-07-013932-9 |page=7{{hyphen}}124<!--HYPHEN PAGE--> }}</ref> used for switching ]s and lighting loads. Continuous current ratings for common contactors range from 10 amps to several hundred amps. High-current contacts are made with alloys containing ]. The unavoidable arcing causes the contacts to oxidize; however, ] is still a good conductor.<ref>{{cite book |title=Electrical control for machines |first1=Kenneth B. |last1=Rexford |first2=Peter R. |last2=Giuliani |edition=6th |publisher=Cengage Learning |year=2002 |isbn=978-0-7668-6198-5 |page=58 |url=https://books.google.com/books?id=5RkbwbYq1joC&pg=PA58}}</ref> Contactors with overload protection devices are often used to start motors.<ref>{{cite web|title=Contactor or Motor Starter – What is the Difference?|url=http://eecoonline.com/contactor-or-motor-starter/|website=EECOOnline.com|access-date=2018-04-19|date=2015-01-13}}</ref> | |||
=== Force-guided contacts relay === | |||
A force-guided contacts relay has relay contacts that are mechanically linked together, so that when the relay coil is energized or de-energized, all of the linked contacts move together. If one set of contacts in the relay becomes immobilized, no other contact of the same relay will be able to move. The function of force-guided contacts is to enable the safety circuit to check the status of the relay. Force-guided contacts are also known as "positive-guided contacts", "captive contacts", "locked contacts", "mechanically linked contacts", or "safety relays". | |||
These safety relays have to follow design rules and manufacturing rules that are defined in one main machinery standard EN 50205 : Relays with forcibly guided (mechanically linked) contacts. These rules for the safety design are the one defined in type B standards such as EN 13849-2 as Basic safety principles and Well-tried safety principles for machinery that applies to all machines. | |||
Force-guided contacts by themselves can not guarantee that all contacts are in the same state, however, they do guarantee, subject to no gross mechanical fault, that no contacts are in opposite states. Otherwise, a relay with several normally open (NO) contacts may stick when energized, with some contacts closed and others still slightly open, due to mechanical tolerances. Similarly, a relay with several normally closed (NC) contacts may stick to the unenergized position, so that when energized, the circuit through one set of contacts is broken, with a marginal gap, while the other remains closed. By introducing both NO and NC contacts, or more commonly, changeover contacts, on the same relay, it then becomes possible to guarantee that if any NC contact is closed, all NO contacts are open, and conversely, if any NO contact is closed, all NC contacts are open. It is not possible to reliably ensure that any particular contact is closed, except by potentially intrusive and safety-degrading sensing of its circuit conditions, however in safety systems it is usually the NO state that is most important, and as explained above, this is reliably verifiable by detecting the closure of a contact of opposite sense. | |||
Force-guided contact relays are made with different main contact sets, either NO, NC or changeover, and one or more auxiliary contact sets, often of reduced current or voltage rating, used for the monitoring system. Contacts may be all NO, all NC, changeover, or a mixture of these, for the monitoring contacts, so that the safety system designer can select the correct configuration for the particular application. Safety relays are used as part of an engineered safety system. | |||
=== Latching relay === | |||
] | |||
A latching relay, also called ''impulse'', ''bistable'', ''keep'', or ''stay'' relay, or simply ''latch'', maintains either contact position indefinitely without power applied to the coil. The advantage is that one coil consumes power only for an instant while the relay is being switched, and the relay contacts retain this setting across a power outage. A latching relay allows remote control of building lighting without the hum that may be produced from a continuously (AC) energized coil. | |||
In one mechanism, two opposing coils with an over-center spring or permanent magnet hold the contacts in position after the coil is de-energized. A pulse to one coil turns the relay on, and a pulse to the opposite coil turns the relay off. This type is widely used where control is from simple switches or single-ended outputs of a control system, and such relays are found in ] and numerous industrial applications. | |||
Another latching type has a ] core that retains the contacts in the operated position by the remanent magnetism in the core. This type requires a current pulse of opposite polarity to release the contacts. A variation uses a permanent magnet that produces part of the force required to close the contact; the coil supplies sufficient force to move the contact open or closed by aiding or opposing the field of the permanent magnet.<ref name="IRS2001">{{citation |last=Sinclair |first=Ian R. |title=Sensors and Transducers |edition=3rd |publisher=Elsevier |date=2001 |isbn=978-0-7506-4932-2 |page=262}}</ref> A polarity controlled relay needs changeover switches or an ] drive circuit to control it. The relay may be less expensive than other types, but this is partly offset by the increased costs in the external circuit. | |||
In another type, a ''ratchet relay'' has a ratchet mechanism that holds the contacts closed after the coil is momentarily energized. A second impulse, in the same or a separate coil, releases the contacts.<ref name="IRS2001"/> This type may be found in certain cars, for ] dipping and other functions where alternating operation on each switch actuation is needed. | |||
A ] is a specialized kind of multi-way latching relay designed for early automatic ]s. | |||
An ] includes a specialized latching relay. | |||
Very ] often stored bits in a magnetically latching relay, such as ] or the later ] in the ]. | |||
{{anchor|Holding circuit}}Some early computers used ordinary relays as a kind of ]—they store bits in ordinary wire-spring relays or reed relays by feeding an output wire back as an input, resulting in a feedback loop or ]. Such an electrically latching relay requires continuous power to maintain state, unlike magnetically latching relays or mechanically ratcheting relays. While '']s'' are often realized with relays they can also be implemented by other means. | |||
In computer memories, latching relays and other relays were replaced by ], which in turn was replaced by a series of ever faster and ever smaller memory technologies. | |||
=== Machine tool relay === | |||
A machine tool relay is a type standardized for industrial control of ]s, transfer machines, and other sequential control. They are characterized by a large number of contacts (sometimes extendable in the field) which are easily converted from normally open to normally closed status, easily replaceable coils, and a ] that allows compactly installing many relays in a control panel. Although such relays once were the backbone of automation in such industries as automobile assembly, the ] (PLC) mostly displaced the machine tool relay from sequential control applications. | |||
A relay allows circuits to be switched by electrical equipment: for example, a timer circuit with a relay could switch power at a preset time. For many years relays were the standard method of controlling industrial electronic systems. A number of relays could be used together to carry out complex functions (]). The principle of relay logic is based on relays which energize and de-energize associated contacts. Relay logic is the predecessor of ], which is commonly used in ]s. | |||
=== Mercury relay === | |||
A ] is a relay that uses mercury as the switching element. They are used where contact erosion would be a problem for conventional relay contacts. Owing to environmental considerations about significant amount of mercury used and modern alternatives, they are now comparatively uncommon. | |||
=== Mercury-wetted relay === | |||
] | |||
A mercury-wetted reed relay is a form of reed relay that employs a ], in which the contacts are wetted with ]. Mercury reduces the contact resistance and mitigates the associated voltage drop. Surface contamination may result in poor conductivity for low-current signals. For high-speed applications, the mercury eliminates contact bounce, and provides virtually instantaneous circuit closure. Mercury wetted relays are position-sensitive and must be mounted according to the manufacturer's specifications. Because of the toxicity and expense of liquid mercury, these relays have increasingly fallen into disuse. | |||
The high speed of switching action of the mercury-wetted relay is a notable advantage. The mercury globules on each contact ], and the current rise time through the contacts is generally considered to be a few picoseconds.{{citation needed|date=November 2023}} However, in a practical circuit it may be limited by the ] of the contacts and wiring. It was quite common, before restrictions on the use of mercury, to use a mercury-wetted relay in the laboratory as a convenient means of generating fast rise time pulses, however although the rise time may be picoseconds, the exact timing of the event is, like all other types of relay, subject to considerable jitter, possibly milliseconds, due to mechanical variations. | |||
The same coalescence process causes another effect, which is a nuisance in some applications. The contact resistance is not stable immediately after contact closure, and drifts, mostly downwards, for several seconds after closure, the change perhaps being 0.5 ohm.{{citation needed|date=November 2023}} | |||
=== Multi-voltage relays === | |||
Multi-voltage relays are devices designed to work for wide voltage ranges such as 24 to 240 VAC and VDC and wide frequency ranges such as 0 to 300 Hz. They are indicated for use in installations that do not have stable supply voltages. | |||
=== Overload protection relay === | |||
Electric motors need ] protection to prevent damage from over-loading the motor, or to protect against short circuits in connecting cables or internal faults in the motor windings.<ref>{{ cite book | last = Zocholl | first = Stan | title = AC Motor Protection | publisher = Schweitzer Engineering Laboratories | year = 2003 | isbn = 978-0972502610 }}</ref> The overload sensing devices are a form of heat operated relay where a coil heats a ], or where a solder pot melts, to operate auxiliary contacts. These auxiliary contacts are in series with the motor's contactor coil, so they turn off the motor when it overheats.<ref>{{cite web|title=Working Principle of Thermal Motor Protection Relay|url=http://electrical-engineering-portal.com/working-principle-of-thermal-motor-protection-relay|website=Electrical-Engineering-Portal.com|publisher=Electrical Engineering Portal|author=Edvard|date=2013-03-09|access-date=2017-12-30}}</ref> | |||
This thermal protection operates relatively slowly allowing the motor to draw higher starting currents before the protection relay will trip. Where the overload relay is exposed to the same ambient temperature as the motor, a useful though crude compensation for motor ambient temperature is provided.<ref>{{cite journal|title=Coordinated Power Systems Protection|issue=811–814|journal=Department of the Army Technical Manual|publisher=]|date=1991|pages=3–1}}</ref> | |||
The other common overload protection system uses an electromagnet coil in series with the motor circuit that directly operates contacts. This is similar to a control relay but requires a rather high fault current to operate the contacts. To prevent short over current spikes from causing nuisance triggering the armature movement is damped with a ]. The thermal and magnetic overload detections are typically used together in a motor protection relay.{{Citation needed|date=December 2017}} | |||
Electronic overload protection relays measure motor current and can estimate motor winding temperature using a "thermal model" of the motor armature system that can be set to provide more accurate motor protection. Some motor protection relays include temperature detector inputs for direct measurement from a ] or ] sensor embedded in the winding.<ref>{{Cite web |date=2020-02-15 |title=Overload relay - Principle of operation, types, connection |url=https://www.electricalclassroom.com/overload-relay-principle-of-operation-types-connection/ |access-date=2022-06-13 |website=www.electricalclassroom.com |language=en-US}}</ref> | |||
=== Polarized relay === | |||
A polarized relay places the armature between the poles of a permanent magnet to increase sensitivity. Polarized relays were used in middle 20th Century ] to detect faint pulses and correct ]. | |||
=== Reed relay === | |||
] | |||
A ] is a ] enclosed in a solenoid. The switch has a set of contacts inside an ] or ]-filled glass tube that protects the contacts against atmospheric ]; the contacts are made of ]ic material that makes them move under the influence of the field of the enclosing solenoid or an external magnet. | |||
Reed relays can switch faster than larger relays and require very little power from the control circuit. However, they have relatively low switching current and voltage ratings. Though rare, the reeds can become magnetized over time, which makes them stick "on", even when no current is present; changing the orientation of the reeds or ] the switch with respect to the solenoid's magnetic field can resolve this problem. | |||
Sealed contacts with mercury-wetted contacts have longer operating lives and less contact chatter than any other kind of relay.<ref name="keller">{{cite journal |last1=Keller |first1=A.C. |date=January 1964 |title=Recent Developments in Bell System Relays — Particularly Sealed Contact and Miniature Relays |url=https://archive.org/details/bstj43-1-15 |journal=The Bell System Technical Journal |volume=43 |issue=1 |pages=15–44 |doi=10.1002/j.1538-7305.1964.tb04057.x |access-date=2023-03-16}}</ref> | |||
=== Safety relays === | |||
]s are devices which generally implement protection functions. In the event of a hazard, the task of such a safety function is to use appropriate measures to reduce the existing risk to an acceptable level.<ref>{{cite web|url=http://www.pilz.com/imperia/md/content/editors_mm/safety_compendium_en_2014_01.pdf|title=Safety Compendium, Chapter 4 Safe control technology|page=115}}</ref> | |||
=== Solid-state contactor === | |||
A solid-state contactor is a heavy-duty solid state relay, including the necessary heat sink, used where frequent on-off cycles are required, such as with electric heaters, small ]s, and lighting loads. There are no moving parts to wear out and there is no contact bounce due to vibration. They are activated by AC control signals or DC control signals from ]s (PLCs), PCs, ] (TTL) sources, or other microprocessor and microcontroller controls. | |||
=== Solid-state relay === | |||
] relays have no moving parts.]] | |||
] | |||
A ] (SSR) is a ] electronic component that provides a function similar to an ] relay but does not have any moving components, increasing long-term reliability. A solid-state relay uses a ], ] or other solid-state switching device, activated by the control signal, to switch the controlled load, instead of a solenoid. An ] (a ] (LED) coupled with a ]) can be used to isolate control and controlled circuits.<ref>{{Cite web|url=https://www.electronics-tutorials.ws/blog/optocoupler.html|title=Optocoupler Tutorial|date=16 September 2013 }}</ref> | |||
=== Static relay === | |||
A ] consists of electronic circuitry to emulate all those characteristics which are achieved by moving parts in an electro-magnetic relay. | |||
=== Time-delay relay === | |||
Timing relays are arranged for an intentional delay in operating their contacts. A very short (a fraction of a second) delay would use a copper disk between the armature and moving blade assembly. Current flowing in the disk maintains a magnetic field for a short time, lengthening release time. For a slightly longer (up to a minute) delay, a dashpot is used. A dashpot is a piston filled with fluid that is allowed to escape slowly; both air-filled and oil-filled dashpots are used. The time period can be varied by increasing or decreasing the flow rate. For longer time periods, a mechanical clockwork timer is installed. Relays may be arranged for a fixed timing period, or may be field-adjustable, or remotely set from a control panel. Modern microprocessor-based timing relays provide precision timing over a great range. | |||
Some relays are constructed with a kind of "shock absorber" mechanism attached to the armature, which prevents immediate, full motion when the coil is either energized or de-energized. This addition gives the relay the property of time-delay actuation. Time-delay relays can be constructed to delay armature motion on coil energization, de-energization, or both. | |||
Time-delay relay contacts must be specified not only as either normally open or normally closed, but whether the delay operates in the direction of closing or in the direction of opening. The following is a description of the four basic types of time-delay relay contacts. | |||
First, we have the normally open, timed-closed (NOTC) contact. This type of contact is normally open when the coil is unpowered (de-energized). The contact is closed by the application of power to the relay coil, but only after the coil has been continuously powered for the specified amount of time. In other words, the direction of the contact's motion (either to close or to open) is identical to a regular NO contact, but there is a delay in closing direction. Because the delay occurs in the direction of coil energization, this type of contact is alternatively known as a normally open, on-delay. | |||
=== Vacuum relays === | |||
A vacuum relay is a sensitive relay having its contacts mounted in an evacuated glass housing, to permit handling radio-frequency voltages {{Clarify|date=August 2022}} as high as 20,000 volts without flashover between contacts even though contact spacing is as low as a few hundredths of an inch when open. | |||
== Applications == | == Applications == | ||
] | |||
Relays are used: | |||
*to control a high-] circuit with a low-voltage signal, as in some types of ]s, | |||
*to control a high-] circuit with a low-current signal, as in the ] ] of an ], | |||
*to detect and isolate faults on transmission and distribution lines by opening and closing circuit breakers (protection relays), | |||
*to isolate the controlling circuit from the controlled circuit when the two are at different potentials, for example when controlling a mains-powered device from a low-voltage switch. The latter is often applied to control office lighting as the low voltage wires are easily installed in partitions, which may be often moved as needs change. They may also be controlled by room occupancy detectors in an effort to conserve energy, | |||
*to perform logic functions. For example, the boolean AND function is realised by connecting relay contacts in series, the OR function by connecting contacts in parallel. Due to the failure modes of a relay compared with a semiconductor, they are widely used in safety critical logic, such as the control panels of radioactive waste handling machinery. | |||
*exceptionally, to generate sound. | |||
A relay can also be made into a ] by wiring the coil in series with the normally-closed contacts. When a current is passed through the relay coil, the relay operates and opens the contacts through which the supply current is passing. This causes the current to stop flowing and the contacts to close again. This cycle repeats continuously, causing the relay to buzz at an audible frequency. This idea has been modified to make an ] by extending the moving contact so it can repeatedly strike a ]. | |||
<br clear = "right"> | |||
] | |||
Relays are used wherever it is necessary to control a high power or high voltage circuit with a low power circuit, especially when ] is desirable. The first application of relays was in long ] lines, whereas the weak signal received at an intermediate station could control a contact, regenerating the signal for further transmission. High-voltage or high-current devices can be controlled with small, low voltage wiring and pilots switches. Operators can be isolated from the high voltage circuit. Low power devices such as ]s can drive relays to control electrical loads beyond their direct drive capability. In an automobile, a starter relay allows the high current of the cranking motor to be controlled with small wiring and contacts in the ignition key. | |||
== Types of relay == | |||
*A '''changeover relay''' has one moving contact (common or C) and two fixed contacts. One of these is ''Normally Closed'' (NC) when the relay is switched off, and the other is ''Normally Open'' (NO). Switching the relay on causes the normally open contact to close and the normally closed contact to open. | |||
Electromechanical switching systems including ] and ] telephone exchanges made extensive use of relays in ancillary control circuits. The Relay Automatic Telephone Company also manufactured telephone exchanges based solely on relay switching techniques designed by ]. The first public relay based telephone exchange in the ] was installed in ] on 15 July 1922 and remained in service until 1959.<ref name="Graces Guide">{{cite web | title = Relay Automatic Telephone Company | url = http://www.gracesguide.co.uk/Relay_Automatic_Telephone_Co | access-date = October 6, 2014}}</ref><ref name="British Telecom History">{{cite web | title = British Telecom History 1912-1968 | url = http://www.btplc.com/thegroup/btshistory/1912to1968/1922.htm | access-date = October 8, 2014 | archive-date = October 14, 2014 | archive-url = https://web.archive.org/web/20141014015809/http://www.btplc.com/thegroup/btshistory/1912to1968/1922.htm | url-status = dead }}</ref> | |||
*A '''latching relay''' is mechanically arranged so that the armature can rest in either of two positions. There are two coils that pull the armature in opposite directions, so the relay can be switched to one position or the other and then left in that state indefinitely. This type of relay has the advantage that it consumes power only for an instant, while it is being switched, and it retains its last setting across a power outage. (Some common relays may be wired to electrically latch, which offers no power saving but does ensure that the relay returns to a known state during and after a power outage.) | |||
*A '''reed relay''' has two, usually normally open, contacts inside a ] or ] filled glass tube. This protects the contacts against atmospheric ]. The two contacts are closed by magnetism from a ] around the glass tube, or a permanent ] moved towards it. See also: ]. | |||
The use of relays for the logical control of complex switching systems like telephone exchanges was studied by ], who formalized the application of ] to relay circuit design in '']''. Relays can perform the basic operations of Boolean combinatorial logic. For example, the Boolean AND function is realised by connecting normally open relay contacts in series, the OR function by connecting normally open contacts in parallel. Inversion of a logical input can be done with a normally closed contact. Relays were used for control of automated systems for machine tools and production lines. The ] is often used for designing ] networks. | |||
*A '''mercury wetted relay''' is a form of reed relay in which the contacts are wetted with ]. Such relays are used to switch low-voltage signals (one volt or less), or for high-speed counting and timing applications where the mercury eliminated contact bounce. Mercury wetted relays are position-sensitive and must be mounted vertically to work properly. Because of the toxicity and expense of liquid mercury, these relays are rarely specified for new equipment. See also ]. | |||
*A '''machine tool relay''' is a type standardized for industrial control of machine tools, transfer machines, and other seqential control. They are characterized by a large number of contacts (sometimes extendable in the field) which are easily converted from normally-open to normally-closed status, easily replaceable coils, and a form factor that allows compactly installing many relays in a control panel. Although such relays once were the backbone of automation in such industries as automobile assembly, the ] mostly displaced the machine tool relay from sequential control applications. | |||
Early ] such as the ], ], ], and ] used relays for logic and working registers. However, electronic devices proved faster and easier to use. | |||
* A '''contactor''' is a very heavy-duty relay used for switching ]s and lighting loads. Such devices are often used for motor starters, and may be built up with overload protection devices attached. | |||
* A ''']''' is a safety device sensing the accumulation of gas in large oil-filled ]s, which will alarm on slow accumulation of gas or shut down the transformer if gas is produced rapidly in the transformer oil. | |||
Relays are much more resistant than semiconductors to nuclear radiation, so they are widely used in safety-critical logic, such as the control panels of radioactive waste-handling machinery. Electromechanical ]s are used to detect overload and other faults on electrical lines by opening and closing ]s. | |||
=== Protective relays === | |||
{{Main|Protective relay}} | |||
For protection of electrical apparatus and transmission lines, electromechanical relays with accurate operating characteristics were used to detect overload, short-circuits, and other faults. While many such relays remain in use, ]s now provide equivalent and more complex protective functions. | |||
=== Railway signaling === | |||
] using UK Q-style miniature plug-in relays]] | |||
] relays are large considering the mostly small voltages (less than 120 V) and currents (perhaps 100 mA) that they switch. Contacts are widely spaced to prevent flashovers and short circuits over a lifetime that may exceed fifty years. | |||
Since rail signal circuits must be highly reliable, special techniques are used to detect and prevent failures in the relay system. To protect against false feeds, ] relay contacts are often used on both the positive and negative side of a circuit, so that two false feeds are needed to cause a false signal. Not all relay circuits can be proved so there is reliance on construction features such as carbon to silver contacts to resist lightning induced contact welding and to provide AC immunity. | |||
]s are also used in some instances with railway signalling, especially where only a single contact is to be switched. | |||
=== Selection considerations === | |||
] and ] telephone exchanges; cover removed on one.]] | |||
==Relay application considerations== | |||
] | |||
Selection of an appropriate relay for a particular application requires evaluation of many different factors: | Selection of an appropriate relay for a particular application requires evaluation of many different factors: | ||
* Number and type of contacts - normally open, normally closed, changeover (double-throw) | |||
* Number and type of contacts — normally open, normally closed, (double-throw) | |||
* Rating of contacts - small relays switch a few amperes, large contactors are rated for up to 3000 amperes, alternating or direct current | |||
* Contact sequence — "make before break" or "break before make". For example, the old style telephone exchanges required make-before-break so that the connection did not get dropped while dialing the number. | |||
* Voltage rating of contacts - typical control relays rated 300 VAC or 600 VAC, automotive types to 50 VDC, special high-voltage relays to about 15,000 V | |||
* Contact current rating — small relays switch a few amperes, large contactors are rated for up to 3000 amperes, alternating or direct current | |||
* Coil voltage - machine-tool relays usually 24 VAC or 120 VAC, relays for switchgear may have 125 V or 250 VDC coils, "sensitive" relays operate on a few milliamperes | |||
* Contact voltage rating — typical control relays rated 300 VAC or 600 VAC, automotive types to 50 VDC, special high-voltage relays to about 15,000 V | |||
* Package/enclosure - open, touch-safe, double-voltage for isolation between circuits, explosion proof, outdoor, oil-splashresistant | |||
* Operating lifetime, useful life — the number of times the relay can be expected to operate reliably. There is both a mechanical life and a contact life. The contact life is affected by the type of load switched. Breaking load current causes ] between the contacts, eventually leading to contacts that weld shut or contacts that fail due to erosion by the arc.<ref name="electronic-components.com.au">{{cite web | title = Arc Suppression to Protect Relays From Destructive Arc Energy | url = http://www.electronic-components.com.au/products-services/arc-suppression/ | access-date = December 6, 2013}}</ref> | |||
* Mounting - sockets, rail mount, panel mount, through-panel mount, enclosure for mounting on walls or equipment | |||
* Coil voltage — machine-tool relays usually 24 VDC, 120 or 250 VAC, relays for switchgear may have 125 V or 250 VDC coils, | |||
* Switching time - where high speed is required | |||
* Coil current — Minimum current required for reliable operation and minimum holding current, as well as effects of power dissipation on coil temperature at various ]s. "Sensitive" relays operate on a few milliamperes. | |||
* "Dry" contacts - when switching very low level signals, special contact materials may be needed such as gold-plated contacts | |||
* Package/enclosure — open, touch-safe, double-voltage for isolation between circuits, ], outdoor, oil and splash resistant, washable for ] assembly | |||
* Contact protection - suppress arcing in very inductive circuits | |||
* Operating environment — minimum and maximum operating temperature and other environmental considerations, such as effects of humidity and salt | |||
* Coil protection - suppress the surge voltage produced when switching the coil current. | |||
* Assembly — Some relays feature a sticker that keeps the enclosure sealed to allow PCB post soldering cleaning, which is removed once assembly is complete. | |||
* Isolation between coil circuit and contacts | |||
* Mounting — sockets, plug board, rail mount, panel mount, through-panel mount, enclosure for mounting on walls or equipment | |||
* Switching time — where high speed is required | |||
* "Dry" contacts — when switching very low level signals, special contact materials may be needed such as gold-plated contacts | |||
* Contact protection — suppress arcing in very inductive circuits | |||
* Coil protection — suppress the surge voltage produced when switching the coil current | |||
* Isolation between coil contacts | |||
* Aerospace or radiation-resistant testing, special quality assurance | * Aerospace or radiation-resistant testing, special quality assurance | ||
* Expected mechanical loads due to ] — some relays used in ] applications are designed to function in ] loads of 50 ], or more. | |||
* Accessories such as timers, auxiliary contacts, pilot lamps, test buttons | |||
* Size — smaller relays often resist mechanical vibration and shock better than larger relays, because of the lower inertia of the moving parts and the higher natural frequencies of smaller parts.<ref name="keller"/> Larger relays often handle higher voltage and current than smaller relays. | |||
* Regulatory approvals | |||
* Accessories such as timers, auxiliary contacts, pilot lamps, and test buttons. | |||
* Regulatory approvals. | |||
* Stray magnetic linkage between coils of adjacent relays on a printed circuit board. | |||
There are many considerations involved in the correct selection of a control relay for a particular application, including factors such as speed of operation, sensitivity, and ]. Although typical control relays operate in the 5 ] to 20 ms range, relays with switching speeds as fast as 100 ] are available. ]s which are actuated by low currents and switch fast are suitable for controlling small currents. | |||
As with any switch, the contact current (unrelated to the coil current) must not exceed a given value to avoid damage. In high-] circuits such as ], other issues must be addressed. When an inductance is connected to a power source, an ] larger than the steady-state current exists. When the circuit is broken, the current cannot change instantaneously, which creates a potentially damaging arc across the separating contacts. | |||
Consequently, for relays used to control inductive loads, we must specify the maximum current that may flow through the relay contacts when it actuates, the ''make rating''; the continuous rating; and the ''break rating''. The make rating may be several times larger than the continuous rating, which is larger than the break rating. | |||
==Protection relay== | |||
A '''protection relay''' is a complex electromechanical apparatus, often with more than one coil, designed to calculate operating conditions on an electrical circuit and trip circuit breakers when a fault was found. Unlike switching type relays with fixed and usually ill-defined operating voltage thresholds and operating times, protection relays had well-established, selectable, time/current (or other operating parameter) curves. Such relays were very elaborate, using arrays of induction disks, shaded-pole magnets, operating and restraint coils, solenoid-type operators, telephone-relay style contacts, and phase-shifting networks to allow the relay to respond to such conditions as over-current, over-voltage, reverse ] flow, over- and under- frequency, and even distance relays that would trip for faults up to a certain distance away from a substation but not beyond that point. An important transmission line or generator unit would have had cubicles dedicated to protection, with a score of individual electromechanical devices. | |||
== Safety and reliability == | |||
Design and theory of these protective devices is an important part of the education of a ] who specializes in power systems. Today these devices are nearly entirely replaced (in new designs) with microprocessor-based instruments (numerical relays) that emulate their electromechanical ancestors with great precision and convenience in application. By combining several functions in one case, numerical relays also save capital cost and maintenance cost over electromechanical relays. However, due to their very long life span, tens of thousands of these "silent sentinels" are still protecting transmission lines and electrical apparatus all over the world. | |||
{{Main|Arc suppression}} | |||
Switching while "wet" (under load) causes undesired arcing between the contacts, eventually leading to contacts that weld shut or contacts that fail due to a buildup of surface damage caused by the destructive arc energy.<ref name="electronic-components.com.au" /> | |||
] | |||
Inside the ] (1ESS) ] and certain other high-reliability designs, the reed switches are always switched "dry" (without load) to avoid that problem, leading to much longer contact life.<ref>{{cite web |first=Al L. |last=Varney |url=http://yarchive.net/phone/1ess.html |title=Questions About The No. 1 ESS Switch |date= 1991}}</ref> | |||
---- | |||
''See also:'' | |||
* ] | |||
* ] | |||
Without adequate ], the occurrence of ] causes significant degradation of the contacts, which suffer significant and visible damage. Every time the relay contacts open or close under load, an electrical arc can occur between the contacts of the relay, either a ''break'' arc (when opening), or a ''make'' / '']'' arc (when closing). In many situations, the ''break'' arc is more energetic and thus more destructive, in particular with inductive loads, but this can be mitigated by bridging the contacts with a ] circuit. The inrush current of tungsten filament incandescent lamps is typically ten times the normal operating current. Thus, relays intended for tungsten loads may use special contact composition, or the relay may have lower contact ratings for tungsten loads than for purely resistive loads. | |||
---- | |||
'''Relay''' is also the name of a series of medium-altitude ]s; the first was launched in ]. | |||
An electrical arc across relay contacts can be very hot — thousands of degrees Fahrenheit — causing the metal on the contact surfaces to melt, pool, and migrate with the current. The extremely high temperature of the arc splits the surrounding gas molecules, creating ], ], and other compounds. Over time, the arc energy slowly destroys the contact metal, causing some material to escape into the air as fine particulate matter. This action causes the material in the contacts to degrade and coordination, resulting in device failure. This contact degradation drastically limits the overall life of a relay to a range of about 10,000 to 100,000 operations, a level far below the mechanical life of the device, which can be in excess of 20 million operations.<ref>{{cite web | title = Lab Note #105: Contact Life — Unsuppressed vs. Suppressed Arcing | publisher = Arc Suppression Technologies | date = April 2011 | url = http://www.arcsuppressiontechnologies.com/arc-suppression-facts/lab-app-notes/ | access-date = October 9, 2011}}</ref> | |||
== |
== See also == | ||
Westinghouse Corporation, ''Applied Protective Relaying'', 1976, Westinghouse Corporation, no ISBN, Library of Congress card no. 76-8060 - a standard reference on electromechanical protection relays (out of print - current edition published by ABB) | |||
* ] | |||
Terrell Croft and Wilford Summers (ed), ''American Electricans' Handbook, Eleventh Edition'', McGraw Hill, New York (1987) ISBN 0070139326 | |||
* ] | |||
==External links== | |||
* ] | |||
Many manfacturers of relays exist. Some commonly used relays are made by the following companies: | |||
* ] | |||
* | |||
* ] | |||
* | |||
* ] | |||
* | |||
* ] | |||
* ] | |||
== References == | |||
{{reflist}} | |||
] | |||
] | |||
] | |||
== External links == | |||
] | |||
] | |||
* {{commons-inline}} | |||
] | |||
] | |||
{{Authority control}} | |||
] | |||
] | |||
] | |||
] | |||
] | |||
] | |||
] | |||
] | |||
] | ] | ||
] | |||
] | |||
] | |||
] |
Latest revision as of 04:36, 27 June 2024
Electrically-operated switch This article is about the electrical component. For other uses, see Relay (disambiguation).A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.
Relays are used where it is necessary to control a circuit by an independent low-power signal, or where several circuits must be controlled by one signal. Relays were first used in long-distance telegraph circuits as signal repeaters: they refresh the signal coming in from one circuit by transmitting it on another circuit. Relays were used extensively in telephone exchanges and early computers to perform logical operations.
The traditional electromechanical form of a relay uses an electromagnet to close or open the contacts, but relays using other operating principles have also been invented, such as in solid-state relays which use semiconductor properties for control without relying on moving parts. Relays with calibrated operating characteristics and sometimes multiple operating coils are used to protect electrical circuits from overload or faults; in modern electric power systems these functions are performed by digital instruments still called protective relays or safety relays.
Latching relays require only a single pulse of control power to operate the switch persistently. Another pulse applied to a second set of control terminals, or a pulse with opposite polarity, resets the switch, while repeated pulses of the same kind have no effects. Magnetic latching relays are useful in applications when interrupted power should not affect the circuits that the relay is controlling.
History
Electrical relays got their start in application to telegraphs. American scientist Joseph Henry is often cited to have invented a relay in 1835 in order to improve his version of the electrical telegraph, developed earlier in 1831.
However, an official patent was not issued until 1840 to Samuel Morse for his telegraph, which is now called a relay. The mechanism described acted as a digital amplifier, repeating the telegraph signal, and thus allowing signals to be propagated as far as desired.
The word relay appears in the context of electromagnetic operations from 1860 onwards.
Basic design and operation
A simple electromagnetic relay consists of a coil of wire wrapped around a soft iron core (a solenoid), an iron yoke which provides a low reluctance path for magnetic flux, a movable iron armature, and one or more sets of contacts (there are two contacts in the relay pictured). The armature is hinged to the yoke and mechanically linked to one or more sets of moving contacts. The armature is held in place by a spring so that when the relay is de-energized there is an air gap in the magnetic circuit. In this condition, one of the two sets of contacts in the relay pictured is closed, and the other set is open. Other relays may have more or fewer sets of contacts depending on their function. The relay in the picture also has a wire connecting the armature to the yoke. This ensures continuity of the circuit between the moving contacts on the armature, and the circuit track on the printed circuit board (PCB) via the yoke, which is soldered to the PCB.
When an electric current is passed through the coil it generates a magnetic field that activates the armature, and the consequent movement of the movable contact(s) either makes or breaks (depending upon construction) a connection with a fixed contact. If the set of contacts was closed when the relay was de-energized, then the movement opens the contacts and breaks the connection, and vice versa if the contacts were open. When the current to the coil is switched off, the armature is returned by a force, approximately half as strong as the magnetic force, to its relaxed position. Usually this force is provided by a spring, but gravity is also used commonly in industrial motor starters. Most relays are manufactured to operate quickly. In a low-voltage application this reduces noise; in a high voltage or current application it reduces arcing.
When the coil is energized with direct current, a flyback diode or snubber resistor is often placed across the coil to dissipate the energy from the collapsing magnetic field (back EMF) at deactivation, which would otherwise generate a voltage spike dangerous to semiconductor circuit components. Such diodes were not widely used before the application of transistors as relay drivers, but soon became ubiquitous as early germanium transistors were easily destroyed by this surge. Some automotive relays include a diode inside the relay case. Resistors, while more durable than diodes, are less efficient at eliminating voltage spikes generated by relays and therefore not as commonly used.
If the relay is driving a large, or especially a reactive load, there may be a similar problem of surge currents around the relay output contacts. In this case a snubber circuit (a capacitor and resistor in series) across the contacts may absorb the surge. Suitably rated capacitors and the associated resistor are sold as a single packaged component for this commonplace use.
If the coil is designed to be energized with alternating current (AC), some method is used to split the flux into two out-of-phase components which add together, increasing the minimum pull on the armature during the AC cycle. Typically this is done with a small copper "shading ring" crimped around a portion of the core that creates the delayed, out-of-phase component, which holds the contacts during the zero crossings of the control voltage.
Contact materials for relays vary by application. Materials with low contact resistance may be oxidized by the air, or may tend to "stick" instead of cleanly parting when opening. Contact material may be optimized for low electrical resistance, high strength to withstand repeated operations, or high capacity to withstand the heat of an arc. Where very low resistance is required, or low thermally-induced voltages are desired, gold-plated contacts may be used, along with palladium and other non-oxidizing, semi-precious metals. Silver or silver-plated contacts are used for signal switching. Mercury-wetted relays make and break circuits using a thin, self-renewing film of liquid mercury. For higher-power relays switching many amperes, such as motor circuit contactors, contacts are made with a mixtures of silver and cadmium oxide, providing low contact resistance and high resistance to the heat of arcing. Contacts used in circuits carrying scores or hundreds of amperes may include additional structures for heat dissipation and management of the arc produced when interrupting the circuit. Some relays have field-replaceable contacts, such as certain machine tool relays; these may be replaced when worn out, or changed between normally open and normally closed state, to allow for changes in the controlled circuit.
Terminology
Since relays are switches, the terminology applied to switches is also applied to relays; a relay switches one or more poles, each of whose contacts can be thrown by energizing the coil. Normally open (NO) contacts connect the circuit when the relay is activated; the circuit is disconnected when the relay is inactive. Normally closed (NC) contacts disconnect the circuit when the relay is activated; the circuit is connected when the relay is inactive. All of the contact forms involve combinations of NO and NC connections.
The National Association of Relay Manufacturers and its successor, the Relay and Switch Industry Association define 23 distinct electrical contact forms found in relays and switches. Of these, the following are commonly encountered:
- SPST-NO (Single-Pole Single-Throw, Normally-Open) relays have a single Form A or make contact. These have two terminals which can be connected or disconnected. Including two for the coil, such a relay has four terminals in total.
- SPST-NC (Single-Pole Single-Throw, Normally-Closed) relays have a single Form B or break contact. As with an SPST-NO relay, such a relay has four terminals in total.
- SPDT (Single-Pole Double-Throw) relays have a single set of Form C, break before make or transfer contacts. That is, a common terminal connects to either of two others, never connecting to both at the same time. Including two for the coil, such a relay has a total of five terminals.
- DPST – Double-Pole Single-Throw relays are equivalent to a pair of SPST switches or relays actuated by a single coil. Including two for the coil, such a relay has a total of six terminals. The poles may be Form A or Form B (or one of each; the designations NO and NC should be used to resolve the ambiguity).
- DPDT – Double-Pole Double-Throw relays have two sets of Form C contacts. These are equivalent to two SPDT switches or relays actuated by a single coil. Such a relay has eight terminals, including the coil
- Form D – make before break
- Form E – combination of D and B
The S (single) or D (double) designator for the pole count may be replaced with a number, indicating multiple contacts connected to a single actuator. For example, 4PDT indicates a four-pole double-throw relay that has 12 switching terminals.
EN 50005 are among applicable standards for relay terminal numbering; a typical EN 50005-compliant SPDT relay's terminals would be numbered 11, 12, 14, A1 and A2 for the C, NC, NO, and coil connections, respectively.
DIN 72552 defines contact numbers in relays for automotive use:
- 85 = relay coil -
- 86 = relay coil +
- 87 = to load (normally open)
- 87a = to load (normally closed)
- 30 = battery +
Types
It has been suggested that this article be split into a new article titled List of relay types. (discuss) (September 2021) |
Coaxial relay
Where radio transmitters and receivers share one antenna, often a coaxial relay is used as a TR (transmit-receive) relay, which switches the antenna from the receiver to the transmitter. This protects the receiver from the high power of the transmitter. Such relays are often used in transceivers which combine transmitter and receiver in one unit. The relay contacts are designed not to reflect any radio frequency power back toward the source, and to provide very high isolation between receiver and transmitter terminals. The characteristic impedance of the relay is matched to the transmission line impedance of the system, for example, 50 ohms.
Contactor
A contactor is a heavy-duty relay with higher current ratings, used for switching electric motors and lighting loads. Continuous current ratings for common contactors range from 10 amps to several hundred amps. High-current contacts are made with alloys containing silver. The unavoidable arcing causes the contacts to oxidize; however, silver oxide is still a good conductor. Contactors with overload protection devices are often used to start motors.
Force-guided contacts relay
A force-guided contacts relay has relay contacts that are mechanically linked together, so that when the relay coil is energized or de-energized, all of the linked contacts move together. If one set of contacts in the relay becomes immobilized, no other contact of the same relay will be able to move. The function of force-guided contacts is to enable the safety circuit to check the status of the relay. Force-guided contacts are also known as "positive-guided contacts", "captive contacts", "locked contacts", "mechanically linked contacts", or "safety relays".
These safety relays have to follow design rules and manufacturing rules that are defined in one main machinery standard EN 50205 : Relays with forcibly guided (mechanically linked) contacts. These rules for the safety design are the one defined in type B standards such as EN 13849-2 as Basic safety principles and Well-tried safety principles for machinery that applies to all machines.
Force-guided contacts by themselves can not guarantee that all contacts are in the same state, however, they do guarantee, subject to no gross mechanical fault, that no contacts are in opposite states. Otherwise, a relay with several normally open (NO) contacts may stick when energized, with some contacts closed and others still slightly open, due to mechanical tolerances. Similarly, a relay with several normally closed (NC) contacts may stick to the unenergized position, so that when energized, the circuit through one set of contacts is broken, with a marginal gap, while the other remains closed. By introducing both NO and NC contacts, or more commonly, changeover contacts, on the same relay, it then becomes possible to guarantee that if any NC contact is closed, all NO contacts are open, and conversely, if any NO contact is closed, all NC contacts are open. It is not possible to reliably ensure that any particular contact is closed, except by potentially intrusive and safety-degrading sensing of its circuit conditions, however in safety systems it is usually the NO state that is most important, and as explained above, this is reliably verifiable by detecting the closure of a contact of opposite sense.
Force-guided contact relays are made with different main contact sets, either NO, NC or changeover, and one or more auxiliary contact sets, often of reduced current or voltage rating, used for the monitoring system. Contacts may be all NO, all NC, changeover, or a mixture of these, for the monitoring contacts, so that the safety system designer can select the correct configuration for the particular application. Safety relays are used as part of an engineered safety system.
Latching relay
A latching relay, also called impulse, bistable, keep, or stay relay, or simply latch, maintains either contact position indefinitely without power applied to the coil. The advantage is that one coil consumes power only for an instant while the relay is being switched, and the relay contacts retain this setting across a power outage. A latching relay allows remote control of building lighting without the hum that may be produced from a continuously (AC) energized coil.
In one mechanism, two opposing coils with an over-center spring or permanent magnet hold the contacts in position after the coil is de-energized. A pulse to one coil turns the relay on, and a pulse to the opposite coil turns the relay off. This type is widely used where control is from simple switches or single-ended outputs of a control system, and such relays are found in avionics and numerous industrial applications.
Another latching type has a remanent core that retains the contacts in the operated position by the remanent magnetism in the core. This type requires a current pulse of opposite polarity to release the contacts. A variation uses a permanent magnet that produces part of the force required to close the contact; the coil supplies sufficient force to move the contact open or closed by aiding or opposing the field of the permanent magnet. A polarity controlled relay needs changeover switches or an H-bridge drive circuit to control it. The relay may be less expensive than other types, but this is partly offset by the increased costs in the external circuit.
In another type, a ratchet relay has a ratchet mechanism that holds the contacts closed after the coil is momentarily energized. A second impulse, in the same or a separate coil, releases the contacts. This type may be found in certain cars, for headlamp dipping and other functions where alternating operation on each switch actuation is needed.
A stepping relay is a specialized kind of multi-way latching relay designed for early automatic telephone exchanges.
An earth-leakage circuit breaker includes a specialized latching relay.
Very early computers often stored bits in a magnetically latching relay, such as ferreed or the later remreed in the 1ESS switch.
Some early computers used ordinary relays as a kind of latch—they store bits in ordinary wire-spring relays or reed relays by feeding an output wire back as an input, resulting in a feedback loop or sequential circuit. Such an electrically latching relay requires continuous power to maintain state, unlike magnetically latching relays or mechanically ratcheting relays. While (self-)holding circuits are often realized with relays they can also be implemented by other means.
In computer memories, latching relays and other relays were replaced by delay-line memory, which in turn was replaced by a series of ever faster and ever smaller memory technologies.
Machine tool relay
A machine tool relay is a type standardized for industrial control of machine tools, transfer machines, and other sequential control. They are characterized by a large number of contacts (sometimes extendable in the field) which are easily converted from normally open to normally closed status, easily replaceable coils, and a form factor that allows compactly installing many relays in a control panel. Although such relays once were the backbone of automation in such industries as automobile assembly, the programmable logic controller (PLC) mostly displaced the machine tool relay from sequential control applications.
A relay allows circuits to be switched by electrical equipment: for example, a timer circuit with a relay could switch power at a preset time. For many years relays were the standard method of controlling industrial electronic systems. A number of relays could be used together to carry out complex functions (relay logic). The principle of relay logic is based on relays which energize and de-energize associated contacts. Relay logic is the predecessor of ladder logic, which is commonly used in programmable logic controllers.
Mercury relay
A mercury relay is a relay that uses mercury as the switching element. They are used where contact erosion would be a problem for conventional relay contacts. Owing to environmental considerations about significant amount of mercury used and modern alternatives, they are now comparatively uncommon.
Mercury-wetted relay
A mercury-wetted reed relay is a form of reed relay that employs a mercury switch, in which the contacts are wetted with mercury. Mercury reduces the contact resistance and mitigates the associated voltage drop. Surface contamination may result in poor conductivity for low-current signals. For high-speed applications, the mercury eliminates contact bounce, and provides virtually instantaneous circuit closure. Mercury wetted relays are position-sensitive and must be mounted according to the manufacturer's specifications. Because of the toxicity and expense of liquid mercury, these relays have increasingly fallen into disuse.
The high speed of switching action of the mercury-wetted relay is a notable advantage. The mercury globules on each contact coalesce, and the current rise time through the contacts is generally considered to be a few picoseconds. However, in a practical circuit it may be limited by the inductance of the contacts and wiring. It was quite common, before restrictions on the use of mercury, to use a mercury-wetted relay in the laboratory as a convenient means of generating fast rise time pulses, however although the rise time may be picoseconds, the exact timing of the event is, like all other types of relay, subject to considerable jitter, possibly milliseconds, due to mechanical variations.
The same coalescence process causes another effect, which is a nuisance in some applications. The contact resistance is not stable immediately after contact closure, and drifts, mostly downwards, for several seconds after closure, the change perhaps being 0.5 ohm.
Multi-voltage relays
Multi-voltage relays are devices designed to work for wide voltage ranges such as 24 to 240 VAC and VDC and wide frequency ranges such as 0 to 300 Hz. They are indicated for use in installations that do not have stable supply voltages.
Overload protection relay
Electric motors need overcurrent protection to prevent damage from over-loading the motor, or to protect against short circuits in connecting cables or internal faults in the motor windings. The overload sensing devices are a form of heat operated relay where a coil heats a bimetallic strip, or where a solder pot melts, to operate auxiliary contacts. These auxiliary contacts are in series with the motor's contactor coil, so they turn off the motor when it overheats.
This thermal protection operates relatively slowly allowing the motor to draw higher starting currents before the protection relay will trip. Where the overload relay is exposed to the same ambient temperature as the motor, a useful though crude compensation for motor ambient temperature is provided.
The other common overload protection system uses an electromagnet coil in series with the motor circuit that directly operates contacts. This is similar to a control relay but requires a rather high fault current to operate the contacts. To prevent short over current spikes from causing nuisance triggering the armature movement is damped with a dashpot. The thermal and magnetic overload detections are typically used together in a motor protection relay.
Electronic overload protection relays measure motor current and can estimate motor winding temperature using a "thermal model" of the motor armature system that can be set to provide more accurate motor protection. Some motor protection relays include temperature detector inputs for direct measurement from a thermocouple or resistance thermometer sensor embedded in the winding.
Polarized relay
A polarized relay places the armature between the poles of a permanent magnet to increase sensitivity. Polarized relays were used in middle 20th Century telephone exchanges to detect faint pulses and correct telegraphic distortion.
Reed relay
A reed relay is a reed switch enclosed in a solenoid. The switch has a set of contacts inside an evacuated or inert gas-filled glass tube that protects the contacts against atmospheric corrosion; the contacts are made of magnetic material that makes them move under the influence of the field of the enclosing solenoid or an external magnet.
Reed relays can switch faster than larger relays and require very little power from the control circuit. However, they have relatively low switching current and voltage ratings. Though rare, the reeds can become magnetized over time, which makes them stick "on", even when no current is present; changing the orientation of the reeds or degaussing the switch with respect to the solenoid's magnetic field can resolve this problem.
Sealed contacts with mercury-wetted contacts have longer operating lives and less contact chatter than any other kind of relay.
Safety relays
Safety relays are devices which generally implement protection functions. In the event of a hazard, the task of such a safety function is to use appropriate measures to reduce the existing risk to an acceptable level.
Solid-state contactor
A solid-state contactor is a heavy-duty solid state relay, including the necessary heat sink, used where frequent on-off cycles are required, such as with electric heaters, small electric motors, and lighting loads. There are no moving parts to wear out and there is no contact bounce due to vibration. They are activated by AC control signals or DC control signals from programmable logic controllers (PLCs), PCs, transistor-transistor logic (TTL) sources, or other microprocessor and microcontroller controls.
Solid-state relay
A solid-state relay (SSR) is a solid state electronic component that provides a function similar to an electromechanical relay but does not have any moving components, increasing long-term reliability. A solid-state relay uses a thyristor, TRIAC or other solid-state switching device, activated by the control signal, to switch the controlled load, instead of a solenoid. An optocoupler (a light-emitting diode (LED) coupled with a photo transistor) can be used to isolate control and controlled circuits.
Static relay
A static relay consists of electronic circuitry to emulate all those characteristics which are achieved by moving parts in an electro-magnetic relay.
Time-delay relay
Timing relays are arranged for an intentional delay in operating their contacts. A very short (a fraction of a second) delay would use a copper disk between the armature and moving blade assembly. Current flowing in the disk maintains a magnetic field for a short time, lengthening release time. For a slightly longer (up to a minute) delay, a dashpot is used. A dashpot is a piston filled with fluid that is allowed to escape slowly; both air-filled and oil-filled dashpots are used. The time period can be varied by increasing or decreasing the flow rate. For longer time periods, a mechanical clockwork timer is installed. Relays may be arranged for a fixed timing period, or may be field-adjustable, or remotely set from a control panel. Modern microprocessor-based timing relays provide precision timing over a great range.
Some relays are constructed with a kind of "shock absorber" mechanism attached to the armature, which prevents immediate, full motion when the coil is either energized or de-energized. This addition gives the relay the property of time-delay actuation. Time-delay relays can be constructed to delay armature motion on coil energization, de-energization, or both.
Time-delay relay contacts must be specified not only as either normally open or normally closed, but whether the delay operates in the direction of closing or in the direction of opening. The following is a description of the four basic types of time-delay relay contacts.
First, we have the normally open, timed-closed (NOTC) contact. This type of contact is normally open when the coil is unpowered (de-energized). The contact is closed by the application of power to the relay coil, but only after the coil has been continuously powered for the specified amount of time. In other words, the direction of the contact's motion (either to close or to open) is identical to a regular NO contact, but there is a delay in closing direction. Because the delay occurs in the direction of coil energization, this type of contact is alternatively known as a normally open, on-delay.
Vacuum relays
A vacuum relay is a sensitive relay having its contacts mounted in an evacuated glass housing, to permit handling radio-frequency voltages as high as 20,000 volts without flashover between contacts even though contact spacing is as low as a few hundredths of an inch when open.
Applications
Relays are used wherever it is necessary to control a high power or high voltage circuit with a low power circuit, especially when galvanic isolation is desirable. The first application of relays was in long telegraph lines, whereas the weak signal received at an intermediate station could control a contact, regenerating the signal for further transmission. High-voltage or high-current devices can be controlled with small, low voltage wiring and pilots switches. Operators can be isolated from the high voltage circuit. Low power devices such as microprocessors can drive relays to control electrical loads beyond their direct drive capability. In an automobile, a starter relay allows the high current of the cranking motor to be controlled with small wiring and contacts in the ignition key.
Electromechanical switching systems including Strowger and crossbar telephone exchanges made extensive use of relays in ancillary control circuits. The Relay Automatic Telephone Company also manufactured telephone exchanges based solely on relay switching techniques designed by Gotthilf Ansgarius Betulander. The first public relay based telephone exchange in the UK was installed in Fleetwood on 15 July 1922 and remained in service until 1959.
The use of relays for the logical control of complex switching systems like telephone exchanges was studied by Claude Shannon, who formalized the application of Boolean algebra to relay circuit design in A Symbolic Analysis of Relay and Switching Circuits. Relays can perform the basic operations of Boolean combinatorial logic. For example, the Boolean AND function is realised by connecting normally open relay contacts in series, the OR function by connecting normally open contacts in parallel. Inversion of a logical input can be done with a normally closed contact. Relays were used for control of automated systems for machine tools and production lines. The Ladder programming language is often used for designing relay logic networks.
Early electro-mechanical computers such as the ARRA, Harvard Mark II, Zuse Z2, and Zuse Z3 used relays for logic and working registers. However, electronic devices proved faster and easier to use.
Relays are much more resistant than semiconductors to nuclear radiation, so they are widely used in safety-critical logic, such as the control panels of radioactive waste-handling machinery. Electromechanical protective relays are used to detect overload and other faults on electrical lines by opening and closing circuit breakers.
Protective relays
Main article: Protective relayFor protection of electrical apparatus and transmission lines, electromechanical relays with accurate operating characteristics were used to detect overload, short-circuits, and other faults. While many such relays remain in use, digital protective relays now provide equivalent and more complex protective functions.
Railway signaling
Railway signalling relays are large considering the mostly small voltages (less than 120 V) and currents (perhaps 100 mA) that they switch. Contacts are widely spaced to prevent flashovers and short circuits over a lifetime that may exceed fifty years.
Since rail signal circuits must be highly reliable, special techniques are used to detect and prevent failures in the relay system. To protect against false feeds, double switching relay contacts are often used on both the positive and negative side of a circuit, so that two false feeds are needed to cause a false signal. Not all relay circuits can be proved so there is reliance on construction features such as carbon to silver contacts to resist lightning induced contact welding and to provide AC immunity.
Opto-isolators are also used in some instances with railway signalling, especially where only a single contact is to be switched.
Selection considerations
Selection of an appropriate relay for a particular application requires evaluation of many different factors:
- Number and type of contacts — normally open, normally closed, (double-throw)
- Contact sequence — "make before break" or "break before make". For example, the old style telephone exchanges required make-before-break so that the connection did not get dropped while dialing the number.
- Contact current rating — small relays switch a few amperes, large contactors are rated for up to 3000 amperes, alternating or direct current
- Contact voltage rating — typical control relays rated 300 VAC or 600 VAC, automotive types to 50 VDC, special high-voltage relays to about 15,000 V
- Operating lifetime, useful life — the number of times the relay can be expected to operate reliably. There is both a mechanical life and a contact life. The contact life is affected by the type of load switched. Breaking load current causes undesired arcing between the contacts, eventually leading to contacts that weld shut or contacts that fail due to erosion by the arc.
- Coil voltage — machine-tool relays usually 24 VDC, 120 or 250 VAC, relays for switchgear may have 125 V or 250 VDC coils,
- Coil current — Minimum current required for reliable operation and minimum holding current, as well as effects of power dissipation on coil temperature at various duty cycles. "Sensitive" relays operate on a few milliamperes.
- Package/enclosure — open, touch-safe, double-voltage for isolation between circuits, explosion proof, outdoor, oil and splash resistant, washable for printed circuit board assembly
- Operating environment — minimum and maximum operating temperature and other environmental considerations, such as effects of humidity and salt
- Assembly — Some relays feature a sticker that keeps the enclosure sealed to allow PCB post soldering cleaning, which is removed once assembly is complete.
- Mounting — sockets, plug board, rail mount, panel mount, through-panel mount, enclosure for mounting on walls or equipment
- Switching time — where high speed is required
- "Dry" contacts — when switching very low level signals, special contact materials may be needed such as gold-plated contacts
- Contact protection — suppress arcing in very inductive circuits
- Coil protection — suppress the surge voltage produced when switching the coil current
- Isolation between coil contacts
- Aerospace or radiation-resistant testing, special quality assurance
- Expected mechanical loads due to acceleration — some relays used in aerospace applications are designed to function in shock loads of 50 g, or more.
- Size — smaller relays often resist mechanical vibration and shock better than larger relays, because of the lower inertia of the moving parts and the higher natural frequencies of smaller parts. Larger relays often handle higher voltage and current than smaller relays.
- Accessories such as timers, auxiliary contacts, pilot lamps, and test buttons.
- Regulatory approvals.
- Stray magnetic linkage between coils of adjacent relays on a printed circuit board.
There are many considerations involved in the correct selection of a control relay for a particular application, including factors such as speed of operation, sensitivity, and hysteresis. Although typical control relays operate in the 5 ms to 20 ms range, relays with switching speeds as fast as 100 μs are available. Reed relays which are actuated by low currents and switch fast are suitable for controlling small currents.
As with any switch, the contact current (unrelated to the coil current) must not exceed a given value to avoid damage. In high-inductance circuits such as motors, other issues must be addressed. When an inductance is connected to a power source, an input surge current or electromotor starting current larger than the steady-state current exists. When the circuit is broken, the current cannot change instantaneously, which creates a potentially damaging arc across the separating contacts.
Consequently, for relays used to control inductive loads, we must specify the maximum current that may flow through the relay contacts when it actuates, the make rating; the continuous rating; and the break rating. The make rating may be several times larger than the continuous rating, which is larger than the break rating.
Safety and reliability
Main article: Arc suppressionSwitching while "wet" (under load) causes undesired arcing between the contacts, eventually leading to contacts that weld shut or contacts that fail due to a buildup of surface damage caused by the destructive arc energy.
Inside the Number One Electronic Switching System (1ESS) crossbar switch and certain other high-reliability designs, the reed switches are always switched "dry" (without load) to avoid that problem, leading to much longer contact life.
Without adequate contact protection, the occurrence of electric current arcing causes significant degradation of the contacts, which suffer significant and visible damage. Every time the relay contacts open or close under load, an electrical arc can occur between the contacts of the relay, either a break arc (when opening), or a make / bounce arc (when closing). In many situations, the break arc is more energetic and thus more destructive, in particular with inductive loads, but this can be mitigated by bridging the contacts with a snubber circuit. The inrush current of tungsten filament incandescent lamps is typically ten times the normal operating current. Thus, relays intended for tungsten loads may use special contact composition, or the relay may have lower contact ratings for tungsten loads than for purely resistive loads.
An electrical arc across relay contacts can be very hot — thousands of degrees Fahrenheit — causing the metal on the contact surfaces to melt, pool, and migrate with the current. The extremely high temperature of the arc splits the surrounding gas molecules, creating ozone, carbon monoxide, and other compounds. Over time, the arc energy slowly destroys the contact metal, causing some material to escape into the air as fine particulate matter. This action causes the material in the contacts to degrade and coordination, resulting in device failure. This contact degradation drastically limits the overall life of a relay to a range of about 10,000 to 100,000 operations, a level far below the mechanical life of the device, which can be in excess of 20 million operations.
See also
- Analogue switch
- Buchholz relay
- Dry contact
- Flyback diode
- Nanoelectromechanical relay
- Race condition
- Stepping switch
- Wire spring relay
References
- Icons of Invention: The Makers of the Modern World from Gutenberg to Gates. ABC-CLIO. 2009. p. 153. ISBN 9780313347436.
- "The electromechanical relay of Joseph Henry". Georgi Dalakov. Archived from the original on 2012-06-18. Retrieved 2012-06-21.
- Scientific American Inventions and Discoveries: All the Milestones in Ingenuity--From the Discovery of Fire to the Invention of the Microwave Oven. John Wiley & Sons. 2005-01-28. p. 311. ISBN 9780471660248.
- Thomas Coulson (1950). Joseph Henry: His Life and Work. Princeton: Princeton University Press.
- US 1647, Morse, Samuel E.B., "Improvement in the Mode of Communicating Information by Signals by the Application of Electromagnetism", published June 20, 1840 "Patent US1647 - IMPROVEMENT IN THE MODE OF COMMUNICATING INFORMATION BY SIGNALS BY THE - Google Patents". Archived from the original on May 24, 2012. Retrieved September 6, 2011.
{{cite web}}
: CS1 maint: bot: original URL status unknown (link) - "Relay". EtymOnline.com.
- "Understanding Relays & Wiring Diagrams". Swe-Check. Retrieved 16 December 2020.
- Mason, C. R. "Art & Science of Protective Relaying, Chapter 2, GE Consumer & Electrical". Retrieved October 9, 2011.
- Riba, J.R.; Espinosa, A.G.; Cusidó, J.; Ortega, J.A.; Romeral, L. (November 2008). Design of Shading Coils for Minimizing the Contact Bouncing of AC Contactors. Electrical Contacts. p. 130. Retrieved 2018-01-07.
- Ian Sinclair, Passive Components for Circuit Design, Elsevier, 2000 ISBN 008051359X, pp. 161–164
- Fleckenstein, Joseph E. (2017). Three-Phase Electrical Power. CRC Press. p. 321. ISBN 978-1498737784.
- Section 1.6, Engineers' Relay Handbook, 5th ed, Relay and Switch Industry Association, Arlington, VA; 3rd ed, National Association of Relay Manufacturers, Elkhart Ind., 1980; 2nd Ed. Hayden, New York, 1966; large parts of the 5th edition are on line here Archived 2017-07-05 at the Wayback Machine.
- ^ Alexandrovich, George. "The Audio Engineer's Handbook" (PDF). Db: The Sound Engineering Magazine. September 1968: 10.
- EN 50005:1976 "Specification for low voltage switchgear and controlgear for industrial use. Terminal marking and distinctive number. General rules." (1976). In the UK published by BSI as BS 5472:1977.
- Ian Sinclair, Passive Components for Circuit Design, Newnes, 2000 ISBN 008051359X, page 170
- Croft, Terrell; Summers, Wilford, eds. (1987). American Electricians' Handbook (Eleventh ed.). New York: McGraw Hill. p. 7-124. ISBN 978-0-07-013932-9.
- Rexford, Kenneth B.; Giuliani, Peter R. (2002). Electrical control for machines (6th ed.). Cengage Learning. p. 58. ISBN 978-0-7668-6198-5.
- "Contactor or Motor Starter – What is the Difference?". EECOOnline.com. 2015-01-13. Retrieved 2018-04-19.
- ^ Sinclair, Ian R. (2001), Sensors and Transducers (3rd ed.), Elsevier, p. 262, ISBN 978-0-7506-4932-2
- Zocholl, Stan (2003). AC Motor Protection. Schweitzer Engineering Laboratories. ISBN 978-0972502610.
- Edvard (2013-03-09). "Working Principle of Thermal Motor Protection Relay". Electrical-Engineering-Portal.com. Electrical Engineering Portal. Retrieved 2017-12-30.
- "Coordinated Power Systems Protection". Department of the Army Technical Manual (811–814). United States Department of the Army: 3–1. 1991.
- "Overload relay - Principle of operation, types, connection". www.electricalclassroom.com. 2020-02-15. Retrieved 2022-06-13.
- ^ Keller, A.C. (January 1964). "Recent Developments in Bell System Relays — Particularly Sealed Contact and Miniature Relays". The Bell System Technical Journal. 43 (1): 15–44. doi:10.1002/j.1538-7305.1964.tb04057.x. Retrieved 2023-03-16.
- "Safety Compendium, Chapter 4 Safe control technology" (PDF). p. 115.
- "Optocoupler Tutorial". 16 September 2013.
- "Relay Automatic Telephone Company". Retrieved October 6, 2014.
- "British Telecom History 1912-1968". Archived from the original on October 14, 2014. Retrieved October 8, 2014.
- ^ "Arc Suppression to Protect Relays From Destructive Arc Energy". Retrieved December 6, 2013.
- Varney, Al L. (1991). "Questions About The No. 1 ESS Switch".
- "Lab Note #105: Contact Life — Unsuppressed vs. Suppressed Arcing". Arc Suppression Technologies. April 2011. Retrieved October 9, 2011.
External links
- Media related to Relay at Wikimedia Commons